NCC 2022 Volume Two - Building Code of Australia Class 1 and 10 buildings
Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

Filter

Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

H6

Part H6 Energy efficiency

Part H6 Energy efficiency

Introduction to this Part

This Part is intended to improve the efficient use of energy in building design and construction, as well as the energy usage by key equipment installed in a building.

Notes

From 1 May 2023 to 30 September 2023 Part 2.6 and Part 3.12 of NCC 2019 Volume Two Amendment 1 may apply instead of Part H6 of NCC 2022 Volume Two. From 1 October 2023 Part H6 of NCC 2022 Volume Two applies.

Objectives

The Objective of this Part is to —

  1. reduce energy consumption and energy peak demand; and
  2. reduce greenhouse gas emissions; and
  3. improve occupant health and amenity.

Functional Statements

A building must—

  1. reduce the energy consumption and energy peak demand of key energy using equipment; and
  2. reduce greenhouse gas emissions that occur as a result of a building’s energy consumption and energy source; and
  3. improve occupant health and amenity by mitigating the impact of extreme hot and cold weather events, and energy blackouts.

Performance Requirements

(1) The total heating load of the habitable rooms and conditioned spaces in a building must not exceed the heating load limit in Specification 44.

(2) The total cooling load of the habitable rooms and conditioned spaces in a building must not exceed the cooling load limit in Specification 44.

(3) The total thermal energy load of the habitable rooms and conditioned spaces in a building must not exceed the thermal energy load limit in Specification 44.

(1) The energy value of a building’s domestic services must not exceed 70% of the energy value with—

  1. a 3-star ducted heat pump, rated under the 2019 GEMS determination, heating all spaces that are provided with heating; and
  2. a 3-star ducted heat pump, rated under the 2019 GEMS determination, cooling all spaces that are provided with cooling; and
  3. a 5-star instantaneous gas water heater, rated under the 2017 GEMS determination, providing all domestic hot water; and
  4. a lighting power density of 4 W/m2 serving all internal spaces that are provided with artificial lighting.

(2) Domestic services, including any associated distribution system and components must, to the degree necessary, have features that facilitate the efficient use of energy appropriate to—

  1. the domestic service and its usage; and
  2. the geographic location of the building; and
  3. the location of the domestic service; and
  4. the energy source.

Verification Methods

NCC Blurbs

The Verification Methods in this Part only apply to—

  1. a Class 1 building; and
  2. an enclosed Class 10a building attached to a Class 1 building.

Notes

The Victorian NCC 2019 rainwater tank variation (VIC V2.6.1 and V3.12.0 respectively) remains in effect until 30 September 2023 after which the following takes effect:

A rainwater tank must be installed in a Class 1 building in accordance with the regulations made under the Building Act 1993 (Victoria).

This Victorian rainwater tank requirement is now found in NCC 2022 Volume Three (Clauses VIC B6D2 and VIC B7D4).

NCC Title

Application of H6V2 and H6V3

NCC State
VIC
NCC Variation Type
Replacement
NCC SPTC Current
Application of H6V2 and H6V3

The Verification Methods in this Part only apply to—

  1. a Class 1 building; and
  2. an enclosed Class 10a building attached to a Class 1 building.

Explanatory information

The Verification Methods in this Part are intended to apply to whole Class 1 buildings and to whole Class 1 buildings that incorporate attached and enclosed Class 10a parts, such as attached garages. The Verification Methods are not intended to apply to detached garages or to open carports.

NCC Title

Verification using a reference building

NCC State
NSW
NCC Variation Type
Deletion
NCC SPTC Current
Verification using a reference building

(1) Compliance with H6P1 is verified when a proposed building—

  1. compared to a reference building, using a calculation method other than house energy rating software, has—
    1. in climate zone 1, a cooling load equal to or less than that of the reference building; or
    2. in climate zone 8, a heating load equal to or less than that of the reference building; or
    3. in climate zones 2, 3, 4, 5, 6 and 7, a heating load and a cooling load equal to or less than that of the reference building; and
  2. complies with—
    1. for building fabric thermal insulation, clause 13.2.2 of the ABCB Housing Provisions; and
    2. for thermal breaks, clauses 13.2.3(7) and 13.2.5(5) of the ABCB Housing Provisions; and
    3. for floor edge insulation, clauses 13.2.6(4), 13.2.6(6) and 13.2.6(7) of the ABCB Housing Provisions; and
    4. for building sealing, Part 13.4 of the ABCB Housing Provisions or H6V3.

(2) The reference building must comply with the Deemed-to-Satisfy Provisions in Parts 13.2, 13.3 and 13.5 of the ABCB Housing Provisions.

(3) The heating load and cooling load for the proposed building and the reference building must be determined using the same—

  1. calculation method; and
  2. location specific data, including that of climate and topography appropriate to the location where the proposed building is to be constructed if the data is available, or the nearest location with similar climatic conditions in the same climate zone for which the data is available; and
  3. impact of adjoining structures and features; and
  4. soil conditions; and
  5. orientation; and
  6. floor plan, including the location and size of glazing; and
  7. number of storeys; and
  8. roof cladding and roof lights; and
  9. separating walls; and
  10. external non-glazed doors; and
  11. intermediate floors; and
  12. floor coverings; and
  13. ventilation; and
  14. function and use of the building and spaces, including zoning and hours of occupation; and
  15. operating schedules for heating and cooling in Table H6V2a; and
  16. cooling thermostat settings of—
    1. for bedrooms, 24°C; and
    2. for habitable rooms other than bedrooms—
      1. in climate zones 1, 2, 3 and 4, 27°C; and
      2. In climate zones 5, 6, 7 and 8, 26°C; and
  17. heating thermostat setting of 20°C for all habitable rooms; and
  18. occupancy in Table H6V2b, with —
    1. heat gains due to occupants of—
      1. 75 W per person in bedrooms; and
      2. 105 W per person in habitable rooms other than bedrooms; and
    2. occupancy schedules in Table H6V2c; and
  19. internal heat gains—
    1. from appliances, 450 W; and
    2. from lighting, 4 W/m²; and
    3. from cooking equipment, in Table H6V2b; and
    4. using the operating schedules for lighting, cooking equipment and appliances, in Table H6V2d; and
  20. air infiltration rate—
    1. of 0.75 air changes per hour; or
    2. equal to the intended building air change rate at 50 Pa, divided by 20, where—
      1. an intended building air change rate at 50 Pa is specified; and
      2. additional building sealing provisions to Part 13.4 of the ABCB Housing Provisions are specified; and
      3. building sealing is verified using H6V3.

(4) The calculation method used must comply with ANSI/ASHRAE Standard 140 and be capable of assessing the heating load and cooling load by modelling—

  1. the building fabric; and
  2. glazing and shading; and
  3. air infiltration and ventilation; and
  4. the function and use of the building including zoning, hours of occupation, hours of heating and cooling availability and internal heat gains; and
  5. relevant built-environment and topographical features; and
  6. the sensible heat component of the cooling load and heating load.

(5) Climatic data employed in the calculation method must be based on hourly recorded values and be representative of a typical year for the proposed location.

Table H6V2a Heating and cooling schedules
Hour ending at Habitable rooms other than bedrooms Bedrooms
1:00 OFF ON
2:00 OFF ON
3:00 OFF ON
4:00 OFF ON
5:00 OFF ON
6:00 OFF ON
7:00 ON ON
8:00 ON ON
9:00 ON ON
10:00 ON OFF
11:00 ON OFF
12:00 ON OFF
13:00 ON OFF
14:00 ON OFF
15:00 ON OFF
16:00 ON OFF
17:00 ON OFF
18:00 ON OFF
19:00 ON ON
20:00 ON ON
21:00 ON ON
22:00 ON ON
23:00 ON ON
0:00 OFF ON
Table H6V2b Occupancy and cooking equipment loads
Floor area of habitable rooms (m²) Occupancy (m²/occupant) Cooking equipment load (W/m² of kitchen area)
100 41.2 36.2
125 44.3 34.7
150 47.8 28.9
175 51.7 24.8
200 55.8 25.3
225 60.0 22.5
250 64.4 20.2
275 68.9 18.4
300 73.3 16.9
325 77.5 15.6
350 81.6 14.5
375 85.4 13.5
400 89.0 12.7
Table H6V2c Occupancy schedules
Hour ending at Weekday occupancy in habitable rooms other than bedrooms Weekend occupancy in habitable rooms other than bedrooms Weekday and weekend bedroom occupancy
1:00 0% 0% 100%
2:00 0% 0% 100%
3:00 0% 0% 100%
4:00 0% 0% 100%
5:00 0% 0% 100%
6:00 0% 0% 100%
7:00 30% 30% 50%
8:00 30% 30% 50%
9:00 100% 30% 50%
10:00 100% 100% 0%
11:00 50% 100% 0%
12:00 50% 100% 0%
13:00 50% 100% 0%
14:00 50% 50% 0%
15:00 50% 50% 0%
16:00 50% 50% 0%
17:00 100% 50% 0%
18:00 100% 50% 0%
19:00 100% 100% 50%
20:00 100% 100% 50%
21:00 100% 100% 50%
22:00 30% 100% 100%
23:00 30% 30% 100%
0:00 0% 0% 100%
Table H6V2d Lighting, cooking and appliance schedules
Hour ending at Lighting Cooking Appliances
1:00 0% 0% 45%
2:00 0% 0% 40%
3:00 0% 0% 40%
4:00 0% 0% 40%
5:00 0% 0% 40%
6:00 0% 0% 40%
7:00 10% 5% 50%
8:00 10% 10% 70%
9:00 5% 10% 55%
10:00 0% 15% 50%
11:00 0% 15% 50%
12:00 0% 15% 50%
13:00 0% 20% 50%
14:00 0% 20% 50%
15:00 0% 20% 50%
16:00 0% 20% 50%
17:00 0% 25% 75%
18:00 20% 40% 95%
19:00 30% 80% 80%
20:00 35% 80% 70%
21:00 30% 40% 70%
22:00 25% 20% 65%
23:00 15% 10% 55%
0:00 0% 5% 55%

(1) Compliance with H6P1 is verified for building envelope sealing when a building envelope is sealed at an air permeability of not more than 10 m3/hr.m2 at 50 Pa reference pressure when tested in accordance with AS/NZS ISO 9972 Method 1.

(2) Where an air permeability of not more than 5 m3/hr.m2 at 50 Pa reference pressure is achieved—

  1. a mechanical ventilation system must be provided that—
    1. can be manually overridden; and
    2. provides outdoor air, either—
      1. continuously; or
      2. intermittently, where the system has controls that enable operation for not less than 25 percent of each 4 hour segment; and
    3. provides a flow rate not less than that achieved with the following formula:
      Q=(0.05×A+3.5×(N+1))/pMathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamyuaiabg2 da9iaacIcacaaIWaGaaiOlaiaaicdacaaI1aaccaGae831aqRaamyq aiabgUcaRiaaiodacaGGUaGaaGynaiab=Dna0kaacIcacaWGobGaey 4kaSIaaGymaiaacMcacaGGPaGaai4laiaadchaaaa@497F@
      , where—
      1. QMathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamyuaaaa@36CA@
        = the required air flow rate (L/s); and
      2. AMathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamyqaaaa@36BA@
        = the total floor area of the building (m²); and
      3. NMathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamOtaaaa@36C7@
        = the number of bedrooms in the building; and
      4. pMathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamiCaaaa@36E9@
        = the fraction of time within each 4 hour segment that the system is operational; and
  2. any space with a solid-fuel burning combustion appliance must be ventilated with permanent openings directly to outside with a free area of not less than half of the cross-sectional area of the appliance’s flue; and
  3. any space with a gas-fuelled combustion appliance must be ventilated in accordance with—
    1. clause 6.4 of AS/NZS 5601.1; and
    2. clause 6.4.5 of AS/NZS 5601.1.

(3) For the purposes of (2)(c), the volume of the space is considered to be 1 m3 for determining ventilation requirements.

Explanatory information

The intent is that 10 m3/hr.m2 at 50 Pa is broadly equivalent to 10 air changes per hour at 50 Pa when applied to homes.

Deemed-to-Satisfy Provisions

(1) Where a Deemed-to-Satisfy Solution is proposed, Performance Requirements H6P1 and H6P2 are satisfied by complying with H6D2.

(2) Where a Performance Solution is proposed, the relevant Performance Requirements must be determined in accordance with A2G2(3) and A2G4(3) as applicable.

NCC Blurbs

(1) Performance RequirementH6P1 for the thermal performance of the building is satisfied by—

  1. complying with S42C2, using house energy rating software and S42C4(1); or
  2. complying with the following parts of the ABCB Housing Provisions—
    1. Part 13.2, for the building fabric; and
    2. Part 13.3, for the external glazing and shading; and
    3. Part 13.4, for building sealing; and
    4. Part 13.5, for ceiling fans.

(2) Performance RequirementH6P2 for the energy usage of the building is satisfied by—

  1. complying with S42C3 using house energy rating software and S42C4(2); or
  2. complying with Parts 13.6 and 13.7 of the ABCB Housing Provisions for a building with a total floor area not greater than 500 m².

Notes: Victorian rainwater tank variation

The Victorian NCC 2019 rainwater tank variation (VIC V2.6.1 and V3.12.0 respectively) remains in effect until 30 September 2023 after which the following takes effect:

A rainwater tank must be installed in a Class 1 building in accordance with the regulations made under the Building Act 1993 (Victoria).

This Victorian rainwater tank requirement is now found in NCC 2022 Volume Three (Clauses VIC B6D2 and VIC B7D4).

Explanatory information

There are two Deemed-to-Satisfy pathways for complying with the energy efficiency Performance Requirements:

  • Option 1 Energy Rating — applying Specification 42 to achieve the heating and cooling loads, net equivalent energy usage, and other energy saving features such as thermal breaks, compensation for a loss of ceiling insulation, floor edge insulation and building sealing.
  • Option 2 Elemental Provisions — using Section 13 of the ABCB Housing Provisions to satisfy all the detailed provisions including building fabric, external glazing, building sealing, ceiling fans, whole-of-home energy usage and services.
NCC Title

Application of Part H6

NCC State
VIC
NCC Variation Type
Replacement
NCC SPTC Current
Application of Part H6

(1) Performance RequirementH6P1 for the thermal performance of the building is satisfied by—

  1. complying with S42C2, using house energy rating software and S42C4(1); or
  2. complying with the following parts of the ABCB Housing Provisions—
    1. Part 13.2, for the building fabric; and
    2. Part 13.3, for the external glazing and shading; and
    3. Part 13.4, for building sealing; and
    4. Part 13.5, for ceiling fans.

(2) Performance RequirementH6P2 for the energy usage of the building is satisfied by—

  1. complying with S42C3 using house energy rating software and S42C4(2); or
  2. complying with Parts 13.6 and 13.7 of the ABCB Housing Provisions for a building with a total floor area not greater than 500 m².

Explanatory information

There are two Deemed-to-Satisfy pathways for complying with the energy efficiency Performance Requirements:

  • Option 1 Energy Rating — applying Specification 42 to achieve the heating and cooling loads, net equivalent energy usage, and other energy saving features such as thermal breaks, compensation for a loss of ceiling insulation, floor edge insulation and building sealing.
  • Option 2 Elemental Provisions — using Section 13 of the ABCB Housing Provisions to satisfy all the detailed provisions including building fabric, external glazing, building sealing, ceiling fans, whole-of-home energy usage and services.