NCC 2022 Volume Three - Plumbing Code of Australia
Search the National Construction Code editions
B4
Part B4 Fire-fighting water servicesPart B4 Fire-fighting water services
This Part sets out requirements for any part of a fire-fighting water service from the point of connection or other acceptable source(s) of supply to the fire-fighting equipment, including hydrants, hose reels, sprinkler services, automatic fire suppression systems and wall drencher systems.
Objectives
B4O1
Objective
2019: BO4
The Objective of this Part is to—
Functional Statements
B4F1
Fire-fighting water supply
2019: BF4
Fire-fighting equipment must be provided with adequate water for its intended purpose.
Performance Requirements
B4P1
Flow rate and pressure
2019: BP4.1
A fire-fighting water service must ensure that the water supply flow and pressures to fire-fighting equipment are to be based on a minimum 95th percentile system performance for the correct functioning of the fire-fighting equipment.
B4P2
Access and isolation
2019: BP4.1
B4P3
Fire-fighting water storage
New for 2022
Water storage supplying fire-fighting systems must be sized suitably for the level of risk and supply arrangements.
B4P4
Uncontrolled discharge
2019: BP4.1
A fire-fighting water service must avoid failure or uncontrolled discharge.
Deemed-to-Satisfy Provisions
B4D1
Deemed-to-Satisfy Provisions
2019: B4.1
B4D2
General requirements
2019: B4.2
General requirements
Fire-fighting water services for Class 2 to Class 9 buildings and structures must comply with the requirements of Part E1 of Volume One of the NCC.
NCC Volume One requires the installation of fire-fighting equipment including fire hose reels, fire hydrants and automatic fire suppression systems in certain types of buildings.
The installation of fire-fighting water services in Class 1 buildings is not required by NCC Volume Two, however, where these services are installed voluntarily, they must be in accordance with Part B4.
B4D3
Fire sprinkler systems
New for 2022
For residential fire sprinklers to FPAA101D Automatic Fire Sprinkler System Design - Drinking water supply, see Part B1 Cold water services.
B4D4
Fire hydrants
New for 2022
Fire hydrants must be in accordance with AS 2419.1.
B4D5
Fire hose reels
New for 2022
Fire hose reels must be in accordance with AS 2441.
B4D6
Bushfire prone areas
New for 2022
Fire-fighting water services in designated bushfire prone areas must be in accordance with AS 3959.
NCC Volumes One and Two deal with a number of areas of on-site construction which are relevant to fire-fighting water services. These include, but may not be limited to, those listed in Table B4.
Item | NCC Volume One Class 2 to 9 buildings | NCC Volume Two Class 1 and 10 buildings |
---|---|---|
Excavations for pipework adjacent to a building and footings | B1 Structural provisions | H1 Structure |
Termite management for attachments to buildings and penetrations through a slab | B1 Structural provisions | H1 Structure |
Penetrations for pipework through a vapour barrier | B1 Structural provisions | H1 Structure |
Pipework in timber bearers and joists of solid timber or engineered wood products | B1 Structural provisions | H1 Structure |
Fittings, fixtures and pipework installations in steel framed construction | B1 Structural provisions | H1 Structure |
Penetrations through a fire-resisting wall or floor | C1 Fire resistance Performance Requirements and C4 Protection of openings | H3 Fire safety |
Fixtures and fittings in a wet area | F2 Wet areas and overflow protection | H4 Health and amenity |
Service pipework external to the building and penetrations through roof cladding in a bushfire prone area | G5 Construction in bushfire prone areas | H7 Ancillary provisions and additional construction requirements |
Flues, chimneys, pipes, gas storage, domestic fuel tanks, cooling or heating appliances or other services | C4 Protection of openings | H3 Fire safety |
Pipework sound insulation | F7 Sound transmission and insulation | H4 Health and amenity |