NCC 2022 Volume Three - Plumbing Code of Australia
Search the National Construction Code editions
41
Specification 41 Cross-connection hazardsSpecification 41 Cross-connection hazards
S41C1
Scope
2019: BS5.1.1
This Specification sets out cross-connection hazards and corresponding Hazard Ratings.
This Specification only prescribes Hazard Ratings for a limited list of known hazards. It does not cover every potential cross-connection that may arise from time to time.
Where a situation arises which is not listed in this Specification, the appropriate Hazard Rating may be determined as a Performance Solution, such as a Performance Solution developed using Verification Method B5V1.
S41C2
Application
2019: BS5.1.2
The Hazard Ratings prescribed in this Specification must be used for selecting the required backflow prevention device, for the purposes of compliance with the Deemed-to-Satisfy Provisions.
S41C3
Protection types and hazard ratings
2019: BS5.1.3
S41C4
Individual protection
2019: BS5.1.4
For the purposes of S41C4(1)(o) in individual protection, clean-in-place is a method of cleaning the internal surfaces of pipes, vessels, process equipment, filters and associated fittings, without disassembly.
For the purposes of S41C4(3)(f), the high hazard backflow prevention device can be part of the toilet douche seat or installed separately.
S41C5
Zone protection
2019: BS5.1.5
S41C6
Containment protection
2019: BS5.1.6
Containment protection
S41C7
Fire-fighting water services
2019: BS5.1.7
Fire hose reels located within an area where a cross-connection hazard exists have a Hazard Rating the same as the areas within reach of the hose.