NCC 2022 Volume Three - Plumbing Code of Australia
Search the National Construction Code editions
B2
Part B2 Heated water servicesPart B2 Heated water services
Year | Tank volume of 400 litres or more and not more than 700 litres | Tank volume of more than 220 litres and less than 400 litres | Tank volume of not more than 220 litres |
---|---|---|---|
2022 | 34 in zone 3* and/or 32 in zone 4 | 24 in zone 3 and/or 23 in zone 4 | 15 in zone 3 and/or 14 in zone 4 |
2023 | 30 in zone 3 and/or 28 in zone 4 | 21 in zone 3 and/or 20 in zone 4 | 13 in zone 3 and/or 12 in zone 4 |
2024 | 26 in zone 3 and/or 25 in zone 4 | 18 in zone 3 and/or 18 in zone 4 | 11 in zone 3 and/or 11 in zone 4 |
2025 | 22 in zone 3 and/or 21 in zone 4 | 16 in zone 3 and/or 15 in zone 4 | 10 in zone 3 and/or 9 in zone 4 |
* Zones are defined by the Clean Energy Regulator
A property is connected to a reticulated gas supply if it has a piped connection to a gas distribution system and this connection is capable of supplying gas to gas equipment and/or appliances.
A property is not connected to a reticulated gas supply if:
Reticulated gas includes:
The energy ratings for natural gas and LPG water heaters are available at: http://www.aga.asn.au/product_directory
STCs are Small-scale Technology Certificates. References to Renewable Energy Certificates (RECs) refer equally to STCs. The number of STCs is provided for each eligible model of solar water heater and electric heat pump water heater at: https://www.cleanenergyregulator.gov.au/RET/Scheme-participants-and-industry/Agents-and-installers/Small-scale-systems-eligible-for-certificates/Register-of-solar-water-heaters
The STC values specified in Section SA B2D2 for either CER Zones 3 or 4 may be used to demonstrate compliance, regardless of the actual zone in which the water heater is to be installed.
Year | Tank volume of 400 litres or more and not more than 700 litres | Tank volume of more than 220 litres and less than 400 litres | Tank volume of not more than 220 litres |
---|---|---|---|
2022 | 34 in zone 3* and/or 32 in zone 4 | 24 in zone 3 and/or 23 in zone 4 | 15 in zone 3 and/or 14 in zone 4 |
2023 | 30 in zone 3 and/or 28 in zone 4 | 21 in zone 3 and/or 20 in zone 4 | 13 in zone 3 and/or 12 in zone 4 |
2024 | 26 in zone 3 and/or 25 in zone 4 | 18 in zone 3 and/or 18 in zone 4 | 11 in zone 3 and/or 11 in zone 4 |
2025 | 22 in zone 3 and/or 21 in zone 4 | 16 in zone 3 and/or 15 in zone 4 | 10 in zone 3 and/or 9 in zone 4 |
* Zones are defined by the Clean Energy Regulator
B2D5 applies to all heated water installations intended for personal hygiene.
Scenarios covered in B2D5 may include where—
Consideration should be given to the intended occupants of a building when commissioning the heated water delivery temperature. For example, if the occupants of a Class 1 building are older adults or young children, a lower temperature than specified in B2D5(b) should be considered.
A duty of care should be exercised by installers to explain to clients the merits of temperature control for heated water delivered to existing sanitary fixtures used primarily for personal hygiene purposes.
A heated water service must be in accordance with AS/NZS 3500.4 with the following variations—