Delete clause C2D4 and insert VIC C2D4 as follows:
(1) A sanitary drainage system must be in accordance with AS/NZS 3500.2; subject to the following—
- insert Clause 4.4.2.1(e): (e) Where an inspection shaft or boundary trap riser in a below ground sanitary drainage system is located clear of a building and is not likely to be damaged by vehicular traffic, a light cover must be installed in accordance with clause 4.4.2.1(a) and clause 4.4.2.1(c)(ii) and (iii).
- insert Clause 4.6.2(d): (d) Have risers installed vertically with no offsets.
- clause 5.3(c) of AS/NZS 3500.2 is varied so that concrete support used to support drains must be provided to support all bends greater than DN 65 to vertical risers.
- replace Clause 5.4.2(d) with: Free running sand, excavated from the trench, capable of passing through a 2 mm mesh sieve, which does not contain clay, organic or other deleterious materials.
- Insert Clause 15.1(b) as follows: Testing of a sanitary drainage installation. If installed at a property provided with non-drinking water by the Network Utility Operator, testing of a sanitary drainage installation may be carried out in accordance with—
- a water test using non-drinking water provided by the Network Utility Operator in accordance with clause 15.2; or
- an air test in accordance with clause 15.3; or
- vacuum test in accordance with clause 15.4; or
- in cases other than in (a), testing may be carried out by way of—
- an air test in accordance with clause 15.3; or
- a vacuum test in accordance with clause 15.4.
(2) Discharge pipes measuring DN 50 or smaller must not be installed in a below ground sanitary drainage system, except for discharge pipes connected to floor waste gullies or vertical riser from a graded drain.