Delete clause B4D2 and insert VIC B4D2 as follows:
(1) Fire-fighting water services for Class 2 to Class 9 buildings and structures must comply with the requirements of Part E1 of Volume One of the NCC.
(2) The installation of a fire-fighting water service must be in accordance with AS/NZS 3500.1.
(3) When installed in Class 1 or Class 10 buildings and structures, an automatic fire sprinkler system must be in accordance with AS 2118.1, AS 2118.4, or AS 2118.5 as appropriate.
(4) Fire-fighting water service work must be in accordance with—
- AS/NZS 1530.3,
- AS 4118.1.1,
- AS 4118.1.2,
- AS 4118.1.3,
- AS 4118.1.4,
- AS 4118.1.5,
- AS 4118.1.6,
- AS 4118.1.7,
- AS 4118.1.8,
- AS 2941,
- AS 2118.2,
- AS 2118.3,
- AS 2118.8,
- AS 2118.10; and
- AS 1851 as appropriate.