(1) Where parts of a Class 1a dwelling are located above a Class 10a private garage that is not associated with the Class 1a dwelling—
any wall separating parts of the Class 1a dwelling from the private garage not associated with the dwelling must comply with (2); and
any private garage associated with and located below the Class 1a dwelling must be separated from the private garage not associated with the dwelling by a wall complying with (2).
(1) Where parts of a Class 1a dwelling are located above or below a Class 10a private garage that is not associated with the Class 1a dwelling, any floor separating the Class 1a dwelling from the Class 10a private garage not associated with the dwelling must—
be a floor/ceiling or floor/soffit system incorporating a ceiling or soffit which has a resistance to the incipient spread of fire to the space above itself of not less than 60 minutes; or
have an FRL not less than 30/30/30 when tested from the underside; or
(2) Where a floor subject to (1)(b) depends on direct vertical or lateral support from another part to maintain its FRL, that supporting part must have an FRL of not less than 30/-/-.
(3) Where a service passes through a floor referred to in (1), the penetration must not reduce the fire performance of the floor or covering.
Notes
Figure 9.4.2 illustrates requirements of this provision.