Insert SA clause 10.2.33 in clause 10.2.33 as follows:
(1) The floor of a wet area containing a vessel must be graded to a floor waste to permit drainage of water.
(2) A floor need not be graded to the floor waste as required by (1) if—
- all vessels are provided with in-built overflow protection or have a permanent open trapped connection to the plumbing and drainage system (such as a WC pan); or
- the floor waste is provided solely for the connection of plumbing fixtures and all vessels in the wet area are provided with in-built overflow protection or have permanent open trapped connection to the plumbing and drainage system (such as a WC pan).
(3) A floor of a wet area that is graded without ponding to a floor waste within the shower area will satisfy (1).
(4) The fall of the floor surface graded to the floor waste in accordance with (1) or (3) must be in accordance with 10.2.12.