13.4
NT Part 13.4 Building sealingNT Part 13.4 Building sealing
This Part applies to—
This Part does not apply to:
The chimney or flue of an open solid-fuel burning appliance must be provided with a damper or flap that can be closed to seal the chimney or flue.
An exhaust fan must be fitted with a sealing device such as a self-closing damper, filter or the like when serving a conditioned space.
An exhaust fan is considered to be adequately sealed if it is fitted with a filter such as the type commonly used in kitchen range hoods.
An evaporative cooler must be fitted with a self-closing damper or the like when serving a heated space.
The self-closing damper should create an effective seal against air infiltration.