5.2
Part 5.2 Masonry veneerPart 5.2 Masonry veneer
5.2.1
Application
New for 2022
5.2.2
Height of wall limitation
2019: 3.3.5.2
Masonry veneer walls must not be greater than 8.5 m in height when measured above the adjacent finished ground level.
5.2.3
Openings in masonry veneer
2019: 3.3.5.11
5.2.4
Damp-proof courses and flashing materials
New for 2022
Damp-proof courses and flashing materials must be in accordance with 5.7.3 and 5.7.4.
5.2.5
Vertical articulation joints
New for 2022
Vertical articulation joints are to be installed in accordance with 5.6.8.
5.2.6
Engaged piers
2019: 3.3.5.14
Where engaged piers are installed to support subfloor framing, they must comply with the provisions of this Part and be constructed as follows: