Part 13.5 Ceiling fansPart 13.5 Ceiling fans
13.5.1
Application of Part 13.5
2019: 3.12.4
13.5.2
Ceiling fans
2019: 3.12.4.3
Ceiling fans must be installed in accordance with Table 13.5.2 in—
Size of room (m²) | Minimum number and diameter (mm) of ceiling fans required in a bedroom in climate zones 1, 2 and 3 | Minimum number and diameter (mm) of ceiling fans required in a habitable room other than a bedroom in climate zones 1, 2, 3 and 5 (NSW and Qld) |
---|---|---|
<15 | 1 x 900 | 1 x 900 |
≥15<20 | 1 x 1200 | 1 x 1200 |
≥20<25 | 1 x 1200 | 1 x 1400 |
≥25<30 | 1 x 1400 | 2 x 1200 |
≥30<45 | 1 x 1400 | 2 x 1400 |
≥45<50 | 2 x 1400 | 3 x 1200 |
≥50 | 2 x 1400 | 3 x 1400 |