ABCB Housing Provisions
Search the National Construction Code editions
10.8
Part 10.8 Condensation managementPart 10.8 Condensation management
10.8.1
External wall construction
2019: 3.8.7.2
10.8.1(2) requires some wall materials on the external side of the primary insulation layer to have a minimum level of vapour permeance. Vapour permeance is measured in µg/N.s (micrograms per newton-second).
Class 3 and Class 4 vapour control membranes (as defined by clause 5.3.4 of AS 4200.1) meet the vapour permeance requirements of 10.8.1(2)(a), while Class 4 vapour control membranes meet the vapour permeance requirements of 10.8.1(2)(b).
Open-cell insulation, such as mineral wool or fibreglass, typically has a high vapour permeance, while closed-cell insulation such as polystyrene typically has a low vapour permeance. Many foil-faced insulation products have a low vapour permeance.
10.8.2
Exhaust systems
2019: 3.8.7.3
A range hood installed in a kitchen must comply with 10.8.2(2).
10.8.2(3) requires venting clothes dryers to be provided with exhaust ducting directly from the clothes dryer to outdoor air. This requirement only applies to venting clothes dryers and not other types of clothes dryers, such as condensing clothes dryers.
10.8.2(5) and 10.8.2(6) requires some rooms that have exhaust systems and are not naturally ventilated (e.g. rooms without openable windows) to be provided with make-up air. The make-up air openings required by 10.8.2(5)(a) are based on the minimum flow rates of 10.8.2(1). An opening with a free area of 14,000 mm2 can by achieved by a 20 mm undercut to a 700 mm wide door. If the exhaust flowrates exceed the minimum flowrates of 10.8.2(1), additional make-up air openings may be required for the correct operation of the exhaust system.
10.8.3
Ventilation of roof spaces
2019: 3.8.7.4
Roof pitch | Ventilation openings |
---|---|
< 10° | 25,000 mm2/m provided at each of two opposing ends |
≥ 10° and < 15° | 25,000 mm2/m provided at the eaves and 5,000 mm2/m at high level |
≥ 15° and < 75° | 7,000 mm2/m provided at the eaves and 5,000 mm2/m at high level, plus an additional 18,000 mm2/m at the eaves if the roof has a cathedral ceiling |
Explanatory Figure 10.8.3 is an example of a roof space with low level ventilation.