ABCB Housing Provisions
Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

Filter

Classification
Building class 1a Building class 1b Building class 2 Building class 3 Building class 4 Building class 5 Building class 6 Building class 7a Building class 7b Building class 8 Building class 9a Building class 9b Building class 9c Building class 10a Building class 10b Building class 10c

5.6

Part 5.6 Masonry components and accessories

Part 5.6 Masonry components and accessories

(1) Part 5.6 is subject to the limitations set out in H1D5(6)(c)(i), (ii) and (iii).

(2) Part 5.6 need not be complied with if H1D5(6)(a) or (b) are complied with.

(1) Masonry veneer masonry units must have a minimum compressive strength of—

  1. 3 MPa for solid or cored units; or
  2. 10 MPa for hollow units.

(2) Cavity masonry and single skin masonry units must have a minimum compressive strength of—

  1. 5 MPa for solid or cored units; or
  2. 10 MPa for hollow units.

(3) Masonry cavity walls must have a minimum leaf thickness of 90 mm.

(4) Subject to (5), masonry units must be—

  1. either clay or calcium silicate brick or concrete brick or block; and
  2. classified and used in the exposure conditions appropriate to their classification as described in (6).

(5) Mixing of panels consisting of clay masonry units with panels consisting of concrete or calcium silicate masonry units is not permitted unless—

  1. at vertical junctions, a control joint is installed; and
  2. at horizontal junctions between panels of different materials, a slip joint using a membrane similar to that used for damp-proof courses is installed.

(6) Masonry unit exposure classifications and corresponding masonry unit applications are as follows:

  1. Protected (P) masonry units are suitable for use in locations such as—
    1. internal walls; and
    2. external walls that are coated or rendered; and
    3. walls above damp-proof courses provided the wall is protected at the top by a roof, eaves, coping, topping or the like.
  2. General Purpose (GP) masonry units are suitable for use in all locations except those where ‘Exposure class’ (Exp) is required.
  3. Exposure class (Exp) masonry units are suitable for use in all locations including severe local conditions such as—
    1. below the damp-proof course in areas where walls are expected to be attacked by salts in the ground water or masonry itself (salt attack or salt damp); and
    2. on sea fronts where walls are exposed to attack from salt spray; and
    3. in heavily polluted areas subject to deposition of atmospheric pollution; and
    4. under regular cyclic freeze and thaw conditions.

Explanatory information

The exposure classification or durability of a masonry unit is a measure of its resistance to attack by soluble salts, either in the ground or in the atmosphere. All masonry products manufactured are classified by their durability. The majority of uses will require either an Exposure class (Exp) product or a General Purpose (GP) product.

Mortar used for masonry construction must comply with AS 3700 or AS 4773 except that the mortar may be mixed by volume in the proportions stated in Table 5.6.3.

Table 5.6.3 Acceptable mortar mixes
Masonry unit exposure classification Mortar mix by volume Note 1 Cement: lime: sand
General use Suitable for concrete masonry Note 2
Protected 1:2:9 1:0:5
General purpose 1:1:6 1:0:5
Exposure class 1:0.5:4.5 1:0:4.2
Table Notes
  1. Additives may be used provided they comply with the appropriate specified rate.
  2. Mortar mixes for masonry require the use of methyl cellulose water thickener.

(1) Unless otherwise specified, masonry bed and perpend joints must have a nominal thickness of 10 mm.

(2) Raked joints are not to be used in saline environments or areas subject to heavy industrial airborne pollution.

(3) Where raked joints are used the depth of raking must not be—

  1. closer than 5 mm to any perforation in cored unit masonry or 20 mm in hollow unit masonry; or
  2. more than 5 mm for masonry units at least 90 mm wide; or
  3. more than 10 mm for masonry units at least 110 mm wide.

Masonry wall ties must—

  1. comply with AS 2699.1 and—
    1. for masonry veneer walls be—
      1. a minimum of light duty veneer ties in areas where the design wind speed is not more than N2; and
      2. a minimum of medium duty veneer ties in areas where the design wind speed is more than N2; and
    2. for cavity masonry walls be—
      1. a minimum of light duty cavity ties in areas where the design wind speed is N1; and
      2. a minimum of medium duty cavity ties in areas where the design wind speed is more than N1; and
    3. where non-engaged piers are provided, piers must be tied to walls using medium duty ties; and
    4. for monolithic or solid masonry construction be a minimum of medium duty ties; and
  2. be spaced and fixed in accordance with Tables 5.6.5a, 5.6.5b and 5.6.5c (see also Figures 5.6.5a and 5.6.5b); and
  3. be protected against corrosion in accordance with Table 5.6.5d.
Table 5.6.5a Wall tie spacings in masonry veneer
Direction Wall tie spacing
450 mm wall stud spacing 600 mm wall stud spacing
Horizontal Maximum 450 mm Maximum 600 mm
Vertical Maximum 600 mm Maximum 400 mm
Table Notes

Wall ties that are suitable for higher duties are also suitable for use in lower duty conditions.

Table 5.6.5b Wall tie spacing in cavity and solid masonry
Direction Wall tie spacing (maximum)
Cavity masonry Solid or monolithic masonry
Horizontal 600 mm 400 mm
Vertical 600 mm 400 mm
Table Notes

Wall ties that are suitable for higher duties are also suitable for use in lower duty conditions.

Table 5.6.5c Placement of wall ties
Location Placement of wall ties
Unsupported panel sides and edges of openings Within 300 mm of panel side or edge
Top of veneer panels and top of panels under openings Within 300 mm or two courses (whichever is the lesser) of the top of veneer
Bottom of veneer panel in masonry rebate sealed with liquid applied damp-proof course Within 300 mm or two courses (whichever is the lesser) from the bottom of the veneer
Bottom of veneer panel supported on steel lintel
Bottom of veneer panel in masonry rebate with membrane damp-proof course In each of the first two courses
Intersection of internal walls and external walls 350 mm vertically or 3-4 courses
Where articulation joints occur At both sides of the articulation joint within 300 mm from the joint
Engaged piers Within 200 mm of the top of the pier
Table Notes
  1. Ties to be embedded a minimum of 50 mm into each masonry leaf.
  2. Masonry wall ties must be installed in such a manner as to prevent moisture travelling along the tie to the inner leaf of masonry or the frame.
Table 5.6.5d Corrosion protection for wall ties
Exposure condition Tie specification (minimum corrosion protection)
Areas less than 1km from breaking surf; or less than 100 m from salt water not subject to breaking surf; or within heavy industrial areas. Grade 316L stainless steel; or engineered polymer complying with the requirements of AS 2699.1.
Areas 1km or more but less than 10km from breaking surf; or 100m or more but less than 1km from salt water not subject to breaking surf. Sheet steel and bar ties galvanised after manufacture - 470 g/m2 on each side; or galvanised wire ties - 470 g/m2 coating mass; or Grade 304L stainless steel.
All other areas Galvanised sheet steel - 300 g/m2 coating on each side; or sheet steel ties galvanised after manufacture - 300 g/m2 on each side.
Figure 5.6.5a Wall tie details (lowset)
image-5-6-5a-wall-tie-details-lowset.svg
Figure 5.6.5b Wall tie details (highset)
image-5-6-5b-wall-tie-details-highset.svg
Figure Notes

Where wall ties are required, they must be placed in adjacent courses (as shown) or must be placed in the same course on each side of the stud.

Explanatory information

Wall ties that are suitable for use in a more severe exposure condition are also suitable for use in less severe exposure conditions, i.e. stainless steel and engineered polymer ties are suitable for use in all conditions and 470g/m2 galvanised ties can be used in all exposure conditions except the most severe.

(1) Timber door and window frames abutting cavity masonry must be fixed with 300 mm long 30 mm x 0.8 mm kinked galvanised steel straps—

  1. fixed to the back of frames; and
  2. set into courses not less than 150 mm at not more than 400 mm intervals.

(2) For areas with a wind class of N1 or N2 and a building width from outside wall to outside wall of not more than 10 m in the direction of the roof span (see Figure 5.6.6a), sheet metal and tiled roofs must be tied down using one of the following methods:

  1. 30 mm x 0.8 mm galvanised steel straps at not more than 1.2 m centres and corresponding with truss or rafter positions, looped around 10 mm diameter galvanised mild steel rods—
    1. built-in across the cavity at a course not less than 900 mm below the top of the wall; and
    2. embedded not less than 50 mm into each leaf.
  2. 30 mm x 1 mm galvanised steel straps at not more than 1.2 m centres and corresponding with truss or rafter positions, built-in to masonry inner leaf not less than 50 mm and at a course not less than 900 mm below the top of the wall (see Figure 5.6.6b).

(3) Roof framing supporting tiled roofs on single leaf unreinforced masonry walls with engaged piers or return walls must have—

  1. a built-in 30 mm x 0.8 mm galvanised steel strap fixed to the roof structure that extends the full height of the engaged pier or return wall; and
  2. a 4.6 grade M12 galvanised steel rod which is cast into the footing when poured and looped and fixed around the galvanised steel strap required by (a) (see Figure 5.6.6c).

(4) Roof framing supporting sheet roofs on single leaf unreinforced masonry with engaged piers or return walls must have—

  1. a built-in 30 mm x 0.8 mm galvanised steel strap fixed to the roof structure extending the full height of the engaged pier or return wall which is looped and fixed around a 4.6 grade 16 mm diameter galvanised steel rod cast into the footing when poured; or
  2. a 4.6 grade M16 galvanised steel rod cast into the footing, threaded at the top and extending the full height of the pier or return wall to connect to the roof structure.
Figure 5.6.6a Building width
image-5-6-6a-building-width.svg
Figure 5.6.6b Suitable tie-down strap details for cavity masonry
image-5-6-6b-suitable-tie-down-strap-details-for-cavity-brick.svg
Figure 5.6.6c Typical tie-down to single leaf unreinforced masonry
image-5-6-6c-typical-tie-down-to-single-leaf-unreinforced-masonry.svg

Explanatory information

Roof tie-down over openings more than 1200 mm wide in masonry construction must be specifically designed in accordance with relevant material and structural design standards.

Where a lintel is required it must comply with the following:

  1. Steel lintels must comply with this Part or H1D6(3).
  2. Steel lintels must—
    1. be sized in accordance with Table 5.6.7a; and
    2. be installed with the long leg of lintel angle vertical; and
    3. be wide enough so that the masonry does not overhang the horizontal leg of the lintel by more than 25 mm; and
    4. not support masonry more than 3 m in height when measured above the opening; and
    5. have a minimum bearing length at each end of the lintel of—
      1. for clear spans not more than 1 m - 100 mm; or
      2. for clear spans more than 1 m - 150 mm (See Figure 5.6.7); and
    6. have a minimum of three courses of masonry over openings; and
    7. comply with the corrosion protection requirements of Table 5.6.7b.
Table 5.6.7a Masonry lintel sizes
Lintel Maximum clear span of lintel (mm): ≤ 600 mm of masonry over opening Maximum clear span of lintel (mm): > 600 mm of masonry over opening
Flat 75 x 8 700 700
Flat 100 x 10 900 900
Angle 90 x 90 x 6EA 3000 2650
Angle 90 x 90 x 8EA 3200 2800
Angle 100 x 100 x 6EA 3350 2900
Angle 100 x 100 x 8EA 3600 3040
Angle 150 x 90 x 8UA 4200 3850
Table Notes

The lintels described in this Table must be not less than grade 300 MPa in accordance with AS 4100.

Table 5.6.7b Corrosion protection – Lintels
Durability class of lintel in accordance with AS 2699.3 Note 1 Material or protective requirements in accordance with AS 2699.3 Note 1
R1, R2 Hot dip galvanised with a minimum average coating thickness of 300 g/m2; or stainless steel 316L
R3 Hot dip galvanised with a minimum average coating thickness of 600 g/m2; or stainless steel 316L
R4 Stainless steel 316L
Table Notes
  1. AS 2699.3 contains information on the corrosivity category locations in Australia and provides a method for determining coating thickness for lintels.
  2. Additional decorative coatings can be applied, but must not be considered for the purpose of satisfying the requirements of this Table.
  3. Any lintel with a coating that is modified, i.e. by cutting, welding, or where damaged, must have the coating restored to provide an equivalent level of protection provided by the original coating.
Figure 5.6.7 Lintel installation
image-5-6-7-lintel-installation.svg

(1) Vertical articulation joints must be provided in masonry walls in accordance with (2), except in walls constructed on sites where the soil classification is A or S (see 4.2.2).

(2) Articulation joints between masonry elements must have a width of not less than 10 mm and be provided (see Figures 5.6.8a and 5.6.8b)—

  1. in straight, continuous walls with openings less than 900 mm x 900 mm or walls without openings — at not more than 6 m centres and within 4.5 m, but not closer than 470 mm of all corners; and
  2. in straight, continuous walls with openings more than 900 mm x 900 mm — at not more than 5 m centres and located so that they are not more than 1.2 m away from openings; and
  3. where the height of the wall changes by more than 20% — at the position of change in height; and
  4. where a wall changes in thickness; and
  5. at control or construction joints in footings or slabs; and
  6. at junctions of walls constructed of different masonry materials.

(3) Articulation joints must not be located adjacent to arched openings.

(4) Articulation joints must be filled with flexible sealant that is supported during installation by—

  1. a compressible foam or polystyrene filler (see Figures 5.6.8d and 5.6.8e); or
  2. a purpose made backer rod (see Figures 5.6.8c, 5.6.8d, 5.6.8e and 5.6.8f).
Figure 5.6.8a Example of vertical articulation joint locations in plan view
image-5-6-8a-example-vertical-articulation-joint-locations-plan-view.svg
Figure 5.6.8b Vertical articulation joints
image-5-6-8b-vertical-articulation-joints.svg
Figure 5.6.8c Articulation joint with backer rod and sealant—single skin masonry and masonry veneer walls
image-5-6-8c-atriculation-joint-with-backer-rod-sealant-single-skin-masonry-masonry-veneer-walls.svg
Figure 5.6.8d Articulation joint in unreinforced single leaf masonry wall with compressed foam
image-5-6-8d-articulation-joint-in-unreinforced-single-leaf-masonry-wall-with-compressed-foam.svg
Figure 5.6.8e Articulation joint in unreinforced masonry veneer wall with compressed foam
image-5-6-8e-articulation-joint-in-unreinforced-masonry-veneer-wall-with-compressed-foam.svg
Figure 5.6.8f Articulation joint in cavity masonry wall
image-5-6-8f-articulation-joint-in-cavity-masonry-wall.svg

Explanatory information

For the purposes of 5.6.8, the vertical articulation joint also performs the function of a contraction or expansion joint.