For a required barrier to an external trafficable structure in an alpine area, the requirements of this Part need to be read in conjunction with the requirements of Part 12.2.
In addition to the requirements of this Part, a barrier and handrail must comply with the structural requirements of Part 2.2. The structural requirements refer to the barrier and/or handrail being designed and constructed to withstand any combinations of loads and other actions to which it may reasonably be subjected and the structural resistance of the materials and forms of construction used for the barrier or handrail.
A window forming a part of a barrier must comply with the glazing assembly provisions of Section 8, and therefore is not required to comply with AS/NZS 1170.1 (structural design actions - referenced in Part 2.2) as it is exempted by Section 8. The Section 8 provisions consider the wind loading on the glazing and human impact requirements.
(1) A continuous barrier must be provided along the side of a trafficable surface, such as—
a stairway, ramp or the like; and
a floor, corridor, hallway, balcony, deck, verandah, mezzanine, access bridge or the like; and
a roof top space or the like to which general access is provided; and
any delineated path of access to a building,
where it is possible to fall 1 m or more measured from the level of the trafficable surface to the surface beneath (see Figure 11.3.3a).
(2) The requirements of (1) do not apply to—
a retaining wall unless the retaining wall forms part of, or is directly associated with, a delineated path of access to a building from the road, or a delineated path of access between buildings (see Figure 11.3.3b); or
a barrier provided to an openable window covered by 11.3.7 and 11.3.8.
Explanatory information: Intent
The intent of the barrier requirements is to prescribe provisions to minimise the risk of a person falling from a stairway, raised floor level (such as a balcony) or the like. 11.3.3 sets out when barriers are required to be provided and 11.3.4 contains the requirements for the construction of barriers.
Explanatory information: Barriers and children
Children are at particular risk of falling off, over or through ineffectively designed or constructed barriers. Accordingly the requirements of this Part aim to ensure that a barrier reduces the likelihood of children being able to climb over a barrier or fall through a barrier.
(1) A barrier required by 11.3.3 must comply with (2) to (11).
(2) The height of a barrier must be in accordance with the following:
The height must not be less than 865 mm above the nosings of the stair treads, the floor of a ramp or the like (see Figure 11.3.4a).
The height must not be less than—
1 m above the floor of any landing, corridor, hallway, balcony, deck, verandah, access path, mezzanine, access bridge, roof top space or the like to which general access is provided (see Figure 11.3.3b and Figure 11.3.4a); or
865 mm above the floor of a landing to a stairway or ramp where the barrier is provided along the inside edge of the landing and does not exceed a length of 500 mm.
(3) A transition zone may be incorporated where the barrier height changes from 865 mm on the stairway flight or ramp to 1 m at the landing (see Figure 11.3.4b).
(4) Openings in barriers (including decorative balustrades) must be constructed so that they do not permit a 125 mm sphere to pass through it and for stairways, the opening is measured above the nosing line of the stair treads (see Figure 11.3.4a).
(5) Where a required barrier is fixed to the vertical face forming an edge of a landing, balcony, deck, stairway or the like, the opening formed between the barrier and the face must not exceed 40 mm.
(6) For the purposes of (5), the opening is measured horizontally from the edge of the trafficable surface to the nearest internal face of the barrier.
(7) A barrier to a stairway serving a non-habitable room, such as an attic, storeroom or the like that is not used on a regular or daily basis, need not comply with (4) if—
openings are constructed so that they do not permit a 300 mm sphere to pass through; or
where rails are used, the barrier consists of a top rail and an intermediate rail, with the openings between rails not more than 460 mm.
(8) Restriction on horizontal elements:
Where it is possible to fall more than 4 m, any horizontal elements within the barrier between 150 mm and 760 mm above the floor must not facilitate climbing.
For the purpose of (a), the 4 m is measured from the floor level of the trafficable surface to the surface beneath.
(9) A barrier constructed of wire is deemed to meet the requirements of (4) if it is constructed in accordance with 11.3.6.
(10) A glass barrier or window serving as a barrier must comply with H1D8 and the relevant provisions of this Part.
(11) A barrier, except a window serving as a barrier, must be designed to take loading forces in accordance with AS/NZS 1170.1.
Explanatory information
For a window forming part of a barrier, any horizontal elements such as a window sill, transom or rail between 150 mm and 760 mm above the floor is deemed to facilitate climbing.
Section 8 contains the glazing assembly provisions for glass barriers and windows forming part of the barrier, however, the barrier would still need to comply with the relevant requirements of this Part for required height, allowable openings, etc.
be located along at least one side of the stairway flight or ramp; and
be located along the full length of the stairway flight or ramp, except in the case where a handrail is associated with a barrier the handrail may terminate where the barrier terminates; and
have the top surface of the handrail not less than 865 mm vertically above the nosings of the stair treads or the floor surface of the ramp (see Figure 11.3.4b); and
be continuous and have no obstruction on or above them that will tend to break a handhold, except for newel posts, ball type stanchions, or the like.
(2) The requirements of (1) do not apply to—
a stairway or ramp providing a change in elevation of less than 1 m; or
a winder where a newel post is installed to provide a handhold.
Explanatory information
11.3.5 addresses requirements regarding location, height and extent of handrails. Where a barrier and handrail are installed together, 11.3.5 is to be read in conjunction with 11.3.3, 11.3.4 and 11.3.6.
A handrail is required on at least one side of the stairway flight or ramp. The top rail of a barrier may be suitable as a handrail if it meets 11.3.5 and is able to be grasped by hand to provide support to the person using the stairway or ramp.
11.3.5(1)(b) requires a continuous handrail which must extend the full length of the stairway flight or ramp except where the handrail is associated with the barrier, in which case the handrail can terminate where the barrier is allowed to terminate. This allows for the barriers to geometric stairways such as elliptical, spiral, circular or curved stairways to finish a few treads from the bottom of the stairway.
11.3.5(1)(c) requires a minimum handrail height of 865 mm. This height provides comfort, stability, support and assistance for most users.
11.3.5(2) outlines where a handrail need not be provided, this includes—
where a stairway or ramp is providing a change in elevation less than 1 m; or
(1) A wire barrier is deemed to meet the requirements of 11.3.4(4) if it is constructed in accordance with (2) to (4).
(2) For a horizontal or near horizontal wire system—
when measured with a strain indicator, it must be in accordance with the tension values in Table 11.3.6a; or
when measured for a maximum permissible deflection, it must not exceed the maximum deflections in Table 11.3.6b.
(3) For a non-continuous vertical wire system—
when measured with a strain indicator, it must be in accordance with the tension values in Table 11.3.6a (see Note 4); or
when measured for maximum permissible deflection, it must not exceed the maximum deflections in Table 11.3.6b.
(4) For a continuous vertical or continuous near vertical sloped wire system—
it must have wires of not more than 2.5 mm diameter with a lay of 7 x 7 or 7 x 19 construction; and
changes in direction at support rails must pass around a pulley block without causing permanent deformation to the wire; and
supporting rails must be spaced of not more than 900 mm apart and be of a material that does not allow deflection that would decrease the tension of the wire under load; and
when the wire tension is measured with a strain indicator, it must be in accordance with the tension values in Table 11.3.6c when measured in the furthermost span from the tensioning device.
Table 11.3.6a Wire barrier construction – Minimum required tension (N) for stainless steel horizontal wire
Wire dia. (mm)
Lay
Wire spacing (mm)
Clear distance between posts (mm)
600
800
900
1000
1200
1500
1800
2000
2500
2.5
7x7
60
55
190
263
415
478
823
1080
1139
x
80
382
630
730
824
1025
1288
x
x
x
100
869
1218
1368
x
x
x
x
x
x
2.5
1x19
60
35
218
310
402
585
810
1125
1325
x
80
420
630
735
840
1050
1400
1750
x
x
100
1140
1565
x
x
x
x
x
x
x
3.0
7x7
60
15
178
270
314
506
660
965
1168
1491
80
250
413
500
741
818
1083
1370
1565
x
100
865
1278
1390
1639
x
x
x
x
x
3.0
1x19
60
25
183
261
340
520
790
1025
1180
x
80
325
555
670
785
1025
1330
1725
1980
x
100
1090
1500
1705
1910
x
x
x
x
x
4.0
7x7
60
5
73
97
122
235
440
664
813
1178
80
196
422
480
524
760
1100
1358
1530
2130
100
835
1182
1360
1528
1837
2381
2811
3098
x
4.0
1x19
60
5
5
10
15
20
147
593
890
1280
80
30
192
300
415
593
1105
1303
1435
1844
100
853
1308
1487
1610
2048
2608
3094
3418
3849
4.0
7x19
60
155
290
358
425
599
860
1080
1285
1540
80
394
654
785
915
1143
1485
1860
2105
2615
100
1038
1412
1598
1785
2165
2735
x
x
x
Table Notes
Lay = number of strands by the individual wires in each strand. For example a lay of 7 x 19 consists of 7 strands with 19 individual wires in each strand.
Where a change of direction is made in a run of wire, the tensioning device is to be placed at the end of the longest span.
If a 3.2 mm diameter wire is used, the tension figures for 3.0 mm wire are applied.
This table may also be used for a set of non-continuous (single) vertical wires forming a barrier using the appropriate clear distance between posts as the vertical clear distance between the rails.
X = not allowed because the required tension would exceed the safe load of the wire.
Tension measured with a strain indicator.
Table 11.3.6b Continuous wire barrier construction – Maximum permissible deflection of each wire in mm when a 2 kg mass is suspended at mid-span for stainless steel wires
Wire dia. (mm)
Wire spacing (mm)
Clear distance between posts (mm)
600
900
1200
1500
1800
2000
2.5
60
17
11
9
8
8
8
80
7
5
5
5
x
x
3.0
60
19
13
8
7
7
7
80
8
6
6
5
5
5
4.0
60
18
12
8
8
7
7
80
8
6
4
4
4
4
Table Notes
Where a change of direction is made in a run of wire, the 2 kg mass must be placed at the middle of the longest span.
If a 3.2 mm diameter wire is used, the deflection figures for a 3.0 mm wire are applied.
This table may also be used for a set of non-continuous (single) vertical wires forming a barrier using the appropriate clear distance between posts as the vertical clear distance between the rails.
The deflection (offset) is measured by hooking a standard spring scale to the mid span of each wire and pulling it horizontally until a force of 19.6 N is applied.
X = not allowed because the required tension would exceed the safe load of the wire.
This table has been limited to 60 mm and 80 mm spaces for 2.5 mm, 3 mm and 4 mm diameter wires because the required wire tensions at greater spacings would require the tension to be beyond the wire safe load limit, or the allowed deflection would be impractical to measure.
Table 11.3.6c Continuous wire barrier construction—Minimum required tension (N) for vertical or near-vertical stainless steel wires where the maximum clear spacing between the rails is 900mm
Wire dia. (mm)
Lay
Wire spacing (mm)
Required tension in Newtons (N)
2.5
7 x 19
80
145
100
310
110
610
2.5
7 x 7
80
130
100
280
110
500
Table Notes
Lay = number of strands by the number of individual wires in each strand. For example a lay of 7 x 19 consists of 7 strands with 19 individual wires in each strand.
Vertical wires must have two pulley blocks to each 180 degree change of direction in the wire.
Near vertical wires may only require one pulley block for each change of direction.
Wire tension measured with a strain indicator.
The table only includes 7 x 7 and 7 x 19 wires due to other wires not having sufficient flexibility to make the necessary turns.
Explanatory information
For the purpose of 11.3.6, a wire barrier consists of a series of tensioned wire rope connected to either vertical or horizontal supports serving as a guard to reduce the risk of a person falling from a roof, stairway, raised floor level or the like.
To assist in the application of 11.3.6, the following terms are explained:
Continuous - where the wire spans three or more supports.
Non-continuous - where the wire only spans between two supports.
Pulley block - a device consisting of a wheel in which a wire runs around to change its direction.
Permissible deflection - is the allowable bending of the wire.
Support rails - are horizontal components of the barrier system that span across the top and bottom to provide structural support.
Tables 11.3.6a and 11.3.6c contain tension requirements for wires in vertical and horizontal wire barrier systems with varying post spacings, wire spacings and wire types, whereas Table 11.3.6b contains deflection requirements for use in horizontal and vertical barrier systems. The figures contained in the tables were derived from testing the spacing combinations in order to prevent the passage of a 125 mm diameter solid cone penetrating between the wires at a predetermined force.
It is important to read the notes to the tables as they provide additional information on their application to horizontal, vertical and near vertical wire barriers.
Wire barriers deflect under loading conditions, even when tightly tensioned. This is particularly relevant over the service life of the barrier as the wire tends to lose its tension. Therefore, care needs to be taken to ensure that wire tension will be maintained during the life of the barrier. In some situations, it may be necessary to incorporate “lock-off” devices to prevent loosening of the wire. Likewise, if a threaded anchor bears against a soft wood post or rail, the anchor may indent the post or rail, thus loosening the wire.
Temperature effects on the tension of the wire may be significant but there is little that can be done to allow for temperature variation in service. The shorter the wire span, the lesser the effect will be.
Stainless steel wire with a lay of 1 x 19 has the greatest elastic modulus and will take up the same load with less extension than equivalent wires with other lays.
A wire barrier excludes wire mesh fences and the like.
Sharp ends of wires at terminations and swages need to be removed for the safety of children and other people. No wire end should protrude more than half the diameter of the wire from the swage or termination fitting.
It should be noted that 11.3.6 is only one form of compliance solution which can be used to demonstrate compliance with H5P2(2)(c) and (d). The following means of verification are available:
not permit a 125 mm sphere to pass through the window opening or screen; and
resist an outward horizontal action of 250 N against the—
window restrained by a device; or
screen protecting the opening; and
have a child resistant release mechanism if the screen or device is able to be removed, unlocked or overridden.
(3) Where a device or screen provided in accordance with (2)(a) is able to be removed, unlocked or overridden, a barrier with a height not less than 865 mm above the floor is required to an openable window in addition to window protection.
(4) A barrier covered by (3) must not—
permit a 125 mm sphere to pass through it; and
have any horizontal or near horizontal elements between 150 mm and 760 mm above the floor that facilitate climbing (see Figure 11.3.7).
Explanatory information: Intent
The intent of 11.3.7 is to reduce the risk of a person (especially a young child) falling through an openable window.
Explanatory information: Protection of openable windows – bedrooms
Where the floor level below an openable window in a bedroom is less than 2 m there are no specific requirements. For an openable window 2 m or more above the surface beneath, openable windows are required to restrict passage of a 125 mm sphere using any one of the following design solutions:
The window be designed such that any opening does not allow a 125 mm sphere to pass through (e.g. louvres) and be capable of resisting a 250 N force when directed against the window.
The window be fitted with a fixed or dynamic device that is capable of restricting the window opening so it does not allow a 125 mm sphere to pass through and is difficult for a young child to operate. The restricting device must be capable of resisting a 250 N force when directed against the window such as a casement window or in attempting to push a sliding window open. An internal screen with similar parameters may be installed.
The window be fitted with an internal or external screen that does not allow a 125 mm sphere to pass through and which must resist a horizontal outward force of 250 N.
If the openable part of the window is at least 1.7 m above the floor, no further protection is required.
Explanatory information: Restricting devices
Where a device or screen is securely fixed in position (e.g. a screen pop riveted to the window frame) so it cannot be unlocked, overridden, or is very difficult to remove without for example a drill, the 865 mm barrier would not be required as the securing method is considered a fixture and not a child resistant release mechanism. 11.3.7(2)(b)(iii) relates to a screen or window restricting device protecting an openable window in a bedroom. The screen or opening restricting device may be installed in a manner that allows it to be removed, unlocked or overridden in the event of a fire or other emergency to allow safe egress. In these situations the unlocking device must be child resistant.
Child resistance could be achieved by the need to use a tool, key or two hands.
There are a number of hardware options available. Short chain winders and barrier screens will allow windows to comply with this requirement. Sliding window locks may lock a sash so a 125 mm sphere cannot pass through. Where provision is made to fully open the window beyond 125 mm then the child resistant release mechanism is required in addition to the device resisting a 250 N force as required by 11.3.7(2)(b)(ii).
11.3.7 in addition prescribes that an 865 mm barrier (sill) would be required. A wall beneath an openable window or fixed glazing under the openable part of a window which meets the height requirements (e.g. transom at least 865 mm above the floor) can be considered as the barrier if the criteria in 11.3.7 are met.
Explanatory information: Use of the term ‘window’
The term “window” is not italicised in 11.3.7 and as such, is not restricted to the definition of “window” in the NCC. The reason for this is to also capture windows that may let in air but not light, e.g. metal louvres. A metal louvre or openable panel would not fit in the NCC definition of window but is subject to the window barrier provisions.
Protection of openable windows – rooms other than bedrooms
2019: 3.9.2.7
(1) A window opening in a room other than a bedroom must be provided with protection where the floor below the window is 4 m or more above the surface beneath.
(2) The openable part of the window covered by (1) must be protected with a barrier with a height of not less than 865 mm above the floor.
have any horizontal or near horizontal elements between 150 mm and 760 mm above the floor that facilitate climbing.
Notes
Figure 11.3.8 illustrates requirements of this provision.
Explanatory information: Intent
The intent of 11.3.8 is to reduce the risk of a person (especially a young child) falling through an openable window.
Explanatory information: Protection of openable windows – rooms other than bedrooms
A wall beneath an openable window or fixed glazing under the openable part of a window which meets the height requirements (e.g. transom at least 865 mm above the floor) can be considered as the barrier, if the criteria in 11.3.8(2) are met.
Explanatory information: Use of the term ‘window’
The term “window” is not italicised in 11.3.8 and as such, is not restricted to the definition of “window” in the NCC. The reason for this is to also capture windows that may let in air but not light, e.g. metal louvres. A metal louvre or openable panel would not fit in the NCC definition of window but is subject to the window barrier provisions.