13.6

Part 13.6 Whole-of-home energy usage

Part 13.6 Whole-of-home energy usage

(1) This Part applies to—

  1. a Class 1 building; and
  2. a Class 10a building with a conditioned space.

(2) Part 13.6 must be applied as directed in H6D2(2).

(1) The net equivalent energy usage of a building, calculated in accordance with (a), must not exceed the allowance calculated in accordance with (b)—

  1. (A×EE)+EP+ESERMathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaaiikaiaadg eaiiaacqWFxdaTcaWGfbWaaSbaaSqaaiaadweaaeqaaOGaaiykaiab gUcaRiaadweadaWgaaWcbaGaamiuaaqabaGccqGHRaWkcaWGfbWaaS baaSqaaiaadofaaeqaaOGaeyOeI0IaamyramaaBaaaleaacaWGsbaa beaaaaa@4422@  
    , where—
    1. AMathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamyqaaaa@36BA@  
      = the floor area factor obtained by multiplying the total floor area of the building by the adjustment factor in Table 13.6.2a; and
    2. EEMathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamyramaaBa aaleaacaWGfbaabeaaaaa@37B4@  
      = the main space conditioning and main water heater efficiency factor obtained from the ABCB Standard for Whole-of-Home Efficiency Factors; and
    3. EPMathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamyramaaBa aaleaacaWGqbaabeaaaaa@37BF@  
      = the swimming pool pump energy usage in (2); and
    4. ESMathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamyramaaBa aaleaacaWGtbaabeaaaaa@37C2@  
      = the spa pump energy usage in (3); and
    5. ERMathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamyramaaBa aaleaacaWGsbaabeaaaaa@37C1@  
      = the installed capacity of on-site photovoltaics (kW); and
  2. A×EFMathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamyqaiabgE na0kaadweadaWgaaWcbaGaamOraaqabaaaaa@3A92@  
    , where—
    1. AMathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamyqaaaa@36BA@  
      = the floor area factor obtained from multiplying the total floor area of the building by the adjustment factor in Table 13.6.2a; and
    2. EFMathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamyramaaBa aaleaacaWGgbaabeaaaaa@37B5@
      = the energy factor obtained from in Table 13.6.2b.

The swimming pool pump energy usage (EP) must be determined in accordance with the following formula:

EP=V×FP/1000MathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamyramaaBa aaleaacaWGqbaabeaakiabg2da9iaadAfaiiaacqWFxdaTcaWGgbWa aSbaaSqaaiaadcfaaeqaaOGaai4laiaaigdacaaIWaGaaGimaiaaic daaaa@4136@  
, where—

  1. EPMathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamyramaaBa aaleaacaWGqbaabeaaaaa@37BF@  
    = the swimming pool pump energy usage; and
  2. VMathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamOvaaaa@36CF@  
    = the volume of the swimming pool to the nearest 1000 litres; and
  3. FPMathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamOramaaBa aaleaacaWGqbaabeaaaaa@37C0@  
    = the swimming pool pump factor as per Table 13.6.2c.

The spa pump energy usage (ES) must be determined in accordance with the following formula:

ES=V×FS/100MathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamyramaaBa aaleaacaWGtbaabeaakiabg2da9iaadAfaiiaacqWFxdaTcaWGgbWa aSbaaSqaaiaadofaaeqaaOGaai4laiaaigdacaaIWaGaaGimaaaa@4082@  
, where—

  1. ESMathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamyramaaBa aaleaacaWGtbaabeaaaaa@37C2@  
    = the spa pump energy usage; and
  2. VMathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamOvaaaa@36CF@  
    = the volume of the spa to the nearest 100 litres; and
  3. FSMathType@MTEF@5@5@+= feaahqart1ev3aqatCvAUfeBSjuyZL2yd9gzLbvyNv2CaerbuLwBLn hiov2DGi1BTfMBaeXatLxBI9gBaerbd9wDYLwzYbItLDharqqtubsr 4rNCHbGeaGqiVu0Je9sqqrpepC0xbbL8F4rqqrFfpeea0xe9Lq=Jc9 vqaqpepm0xbba9pwe9Q8fs0=yqaqpepae9pg0FirpepeKkFr0xfr=x fr=xb9adbaqaaeGaciGaaiaabeqaamaabaabaaGcbaGaamOramaaBa aaleaacaWGtbaabeaaaaa@37C3@  
    = the spa pump factor as per Table 13.6.2d.
    Table 13.6.2a Floor area adjustment factor
    Total floor area m2 Floor area factor Total floor area m2 Floor area factor Total floor area m2 Floor area factor Total floor area m2 Floor area factor
    <50 0.0123 160–169 0.0097 280–289 0.0087 400–409 0.0080
    50–59 0.0119 170–179 0.0096 290–299 0.0086 410–419 0.0079
    60–69 0.0116 180–189 0.0095 300–309 0.0085 420–429 0.0079
    70–79 0.0113 190–199 0.0094 310–319 0.0085 430–439 0.0078
    80–89 0.0111 200–209 0.0093 320–329 0.0084 440–449 0.0078
    90–99 0.0108 210–219 0.0092 330–339 0.0083 450–459 0.0077
    100–109 0.0106 220–229 0.0091 340–349 0.0083 460–469 0.0077
    110–119 0.0105 230–239 0.0090 350–359 0.0082 470–479 0.0077
    120–129 0.0103 240–249 0.0090 360–369 0.0082 480–489 0.0076
    130–139 0.0101 250–259 0.0089 370–379 0.0081 490–499 0.0076
    140–149 0.0100 260–269 0.0088 380–389 0.0081 500 0.0075
    150–159 0.0099 270–279 0.0087 390–399 0.0080
    Table Notes
    1. The total floor area is measured within the inside face of the external walls of the Class 1 building and includes any conditioned, attached Class 10a building.
    2. Where values fall between ranges given, the floor area must be rounded up to the nearest whole square metres of floor area.
    Table 13.6.2b Energy factor (EF)
    Climate zone ACT NSW NT Qld SA Tas Vic WA
    1 1.91 2.77 3.25
    2 1.32 1.78
    3 1.23 2.46 2.87
    4 1.80 1.86 1.25 2.34
    5 1.75 2.28 1.79 2.35
    6 2.40 2.51 1.63 3.20
    7 2.56 2.33 3.08 1.62
    8 3.99 3.92 2.82
    Table 13.6.2c Swimming pool pump factor (FP) (kW/1000 litres.annum)
    Pool pump GEMS star rating ACT NSW NT Qld SA Tas Vic WA
    1 or unrated 0.056 0.060 0.028 0.046 0.068 0.061 0.049 0.063
    1.5 0.048 0.050 0.023 0.039 0.057 0.052 0.041 0.053
    2 0.041 0.044 0.020 0.034 0.050 0.045 0.036 0.046
    2.5 0.037 0.039 0.018 0.030 0.044 0.040 0.032 0.041
    3 0.033 0.035 0.016 0.027 0.039 0.035 0.028 0.036
    3.5 0.029 0.031 0.014 0.024 0.035 0.032 0.025 0.033
    4 0.026 0.028 0.013 0.021 0.032 0.029 0.023 0.029
    4.5 0.024 0.025 0.012 0.019 0.029 0.026 0.021 0.027
    5 0.022 0.023 0.011 0.018 0.026 0.023 0.019 0.024
    5.5 0.020 0.021 0.010 0.016 0.023 0.021 0.017 0.022
    6 0.018 0.019 0.009 0.014 0.021 0.019 0.015 0.020
    6.5 0.016 0.017 0.008 0.013 0.019 0.017 0.014 0.018
    7 0.014 0.015 0.007 0.012 0.017 0.016 0.012 0.016
    7.5 0.013 0.013 0.006 0.010 0.015 0.014 0.011 0.014
    8 0.011 0.012 0.006 0.009 0.014 0.012 0.010 0.013
    8.5 0.010 0.011 0.005 0.008 0.012 0.011 0.009 0.011
    9 0.009 0.009 0.004 0.007 0.011 0.010 0.008 0.010
    9.5 0.008 0.008 0.004 0.006 0.009 0.008 0.007 0.009
    10 0.007 0.007 0.003 0.005 0.008 0.007 0.006 0.007
    Table 13.6.2d Spa pump factor (FS) (kW/100 litres.annum)
    Spa pump GEMS star rating ACT NSW NT Qld SA Tas Vic WA
    All types 0.067 0.071 0.033 0.055 0.081 0.073 0.058 0.075

Explanatory information

The ABCB Standard for Whole-of-Home Efficiency Factors can be accessed at www.abcb.gov.au.