This video from the 2022 NCC Seminars discusses the changes to the Performance Requirements for NCC 2022 Volume Three.

Transcript

0:00

foreign [Music]  

0:14

Now let's get into the nuts and bolts. I will  

0:16

take you through the changes to the  Performance Requirements of the PCA.

0:22

First thing I know you're going to ask - what is  quantification? Quantification is the expression  

0:28

or measurement of something, and you will see  what I mean as we work our way through them.  

0:33

A large amount of work has been undertaken in  reviewing the performance requirements of the PCA  

0:38

to ensure that these high-level objectives of the  

0:41

Code set out a measurable target to meet  when undertaking a Performance Solution.  

0:46

Quantified Performance Requirements will make it  simpler to know if the solution being used will  

0:51

meet these requirements as well as it being easier  for a regulator to confirm that solution complies.  

0:59

The amended Performance Requirements are what  we call a policy neutral change. This means that  

1:04

whilst the clause was changed the technical  objective has not. This is still a work in  

1:10

progress although, however, with a number of  Performance Requirements still to be identified,  

1:14

but over the next few slides I'll step you through  the changes so far to the requirements of 2022.

1:20

The first Performance Requirement relates to  the flow rates of a cold water service. As  

1:25

you can see, the 2019 requirement didn't  really give you much to work towards,  

1:29

and determining the appropriate flow rates for  the correct functioning of fixtures is tricky.  

1:35

The 2022 requirement is a lot more specific,  outlining a limit of 3 meters per second.  

1:41

The reference to one percent refers to how much  time that the system would be expected to exceed  

1:47

this maximum velocity during the period of peak  use which is referred to as the annual peak hour.

1:54

This one is another great example. It could be  difficult to demonstrate that you have designed  

1:59

a service to efficiently use drinking water.  However, it is easy to ensure that your showers,  

2:04

basins and sinks use no more than 9 litres per  minute or that the toilets being used flush no  

2:10

more than 6 and 3, or 4.5 and 3 litres. You'll  see that subclause B, however, at the bottom,  

2:18

also allows for flexibility should a  Performance solution require. However,  

2:22

it still works in conjunction with the first part  to provide a means of compliance measurement.

2:29

This one is for pressure. The required pressures  of a water service is also another area which  

2:35

has received some attention in 2022 points.  This change has provided a limit of between  

2:40

50 kPa and 500 kPa which gives you a parameter  and is much easier to demonstrate compliance.  

2:47

You will see that the second  subclause, subclause B,  

2:50

will continue to provide the flexibility if  you need to work outside of these pressures.

2:57

This one is about heated water services.  Heated water flow rates have received the same  

3:01

treatment as cold water services. This Performance  Requirement has been broken down into reticulated  

3:07

systems and circulatory systems. Circulatory  systems have been then separated between  

3:12

copper systems and other pipework materials  as they can cater for different velocities.

3:20

This one is about excessive pressure,  for the temperature and pressure relief  

3:24

of water heaters. If you look at the 2019  requirement you might be a bit stumped on  

3:29

what is considered excessive pressure or  what temperatures you need to limit the  

3:33

system to in order to prevent flash steam  production. Now with the quantification,  

3:38

a specific temperature and pressure is listed,  and again there is a degree of flexibility if  

3:43

that performance solution being used needs  to deviate beyond beyond these limits.

3:49

Legionella is a major ongoing  issue in warm water so another  

3:53

area which has been updated is the  requirement for Legionella control.  

3:57

The Performance Requirement now sets a target  Legionella count that a heated water system must  

4:02

be designed to achieve. This limit aligns with  the advice provided by the health departments.

4:09

With this fire-fighting water service  provision you can see that this requirement  

4:13

is set at the 95th percentile, not one  percent as per the cold water service.  

4:18

This works the same way but rather than exceeding  no more than one percent of the time or operating  

4:23

correctly 99 per cent of the time, this  requirement sets a 95 per cent target.  

4:28

This provides an additional safety factor  for fire-fighting water services to ensure  

4:33

that the service pressures and the flow rates  for fire-fighting water service are correct.  

4:38

The safety factor is important, as having the  right flow rates and pressures is critical in  

4:43

ensuring that the fire-fighting water  service works when it is needed.

4:47

And the last example is for factory plumbing  ventilation. As you can see, the quantified  

4:52

Performance Requirement provides a limit of both  positive and negative pressures within the system.  

4:58

This pressure limitation is to set to  ensure the trap seals are not affected  

5:02

and continue to prevent the escape of sewer  gases into the building. This requirement  

5:08

obviously does not apply to a vacuum drainage  system which operates in a negative pressure.

5:13

This is the last quantification example I  have for you but watch this space for 2025  

5:18

as we continue to work our way through  the Performance Requirements of the PCA.